Mitsubishi Electric NZ2FTGN User Manual page 289

Slice remote i/o module
Table of Contents

Advertisement

■Creating Reference list
Create Reference list in the latched area.
The following describes how to create Reference list using an example of creating a file register (ZR) of the CPU module.
1.
In GX Works2, set the file register as follows.
[Parameter]  [PLC Parameter]  [PLC File]
Item
Use the following file
Corresponding Memory
File Name
Capacity
For details on setting the file register, refer to the following.
 QnUCPU User's Manual (Functional Explanation/Program Basics)
2.
The watch window is displayed.
[View]  [Docking Window]  [Watch 1] to [Watch 4]
3.
Set the "Data Type" to "Double Word[Unsigned]/Bit String[32-bit]" and set Module ID according to the system
configuration. (Set Module ID in hexadecimal.)
Device/label
Current value
ZR0000
H15C40401
ZR0002
H25E00506
ZR0004
H1F840009
ZR0006
H2FA00101
ZR0008
HFFFFFFFF
*1 Indicates Module ID when the data format is in Motorola format. For details on changing the data format, refer to the following.
Page 304 Parameter list
For Module ID of each I/O module, refer to the following.
Page 591 Module ID list
Setting details
Check this item.
Standard RAM (Drive 3)
REF_LIST
3
(Module ID (2 words)  Maximum number of connectable I/O modules (64)  Maximum number of connectable
stations (20) = 2560 words  3K)
*1
Description
Module ID of the NZ2FTS-60AD4
Module ID of the NZ2FTS-60DA4
Module ID of the NZ2FTS4-4DE
Module ID of the NZ2FTS4-4TE
The program for writing Reference list includes processing to reduce the number of loops in the
program when the number of I/O modules is less than 64. Therefore, set FFFFFFFFH as the end code
next to the I/O module mounted last.
11
11 NZ2FT-MT
287
11.4 Functions

Advertisement