Saving/loading parameter files

When replacing the coupler, save the parameters of the coupler and I/O module in a file. Also, load the saved parameters
from the file.
Operating procedure
■Saving parameter files
1.
Select "Stations parameters" or "Save/load configuration" from the [Extras] menu.
2.
Click the [Save] button.
The parameter file is downloaded from the Web server. (The file name cannot be specified.)
■Loading parameter files
1.
Select "Stations parameters" or "Save/load configuration" from the [Extras] menu.
2.
Click the [Load] button.
3.
Select the saved parameter file and click the [Open] button.
In the following cases, the parameter file cannot be loaded.
• When the system configuration of the saved parameter file is different from the actual system configuration (Including the
case of loading the parameter file saved by the coupler of a different model)
• When the saved parameter file is damaged
• When the master station and the coupler are communicating I/O data (BF LED turns off)
4.
Click the [Reset] button on the "load configuration" window to reset the coupler.
Parameters to be saved/loaded
: Target, : Not applicable
■NZ2FT-GN
Parameter
IP address
Subnet mask
IP address USB port
Webserver via Ethernet
HTTPS setting
Process alarm
Diagnostic alarm
Output behaviour on fieldbus error
Module behaviour on hot swap
Data format
4 WEB SERVER
80
4.3 Functions to Set on the Web Server
Save/load