Parameter List - Mitsubishi Electric NZ2FTGN User Manual

Slice remote i/o module
Table of Contents

Advertisement

Parameter list

These parameters can be set in the NZ2FT-GN from the Web server or GX Works3 of the master station.
: Can be set, : Cannot be set
Item
Description
IP address
Set the IP address of the USB port.
USB port
IP address
When the IP address setting switch is 0, the IP address of the NZ2FT-
GN is set.
Do not set the values out of the setting range.
Subnet mask
Set the subnet mask of the NZ2FT-GN.
When connected to the master station, operation is performed with the
subnet mask of the master station until the NZ2FT-GN is turned off and
on.
Do not set the values out of the setting range.
Webserver via
Set whether to enable or disable the access to the Web server via the
Ethernet
Ethernet port.
The NZ2FT-GN must be reset after the setting.
Process alarm
Set whether to detect Process alarm that occurred in the I/O module.
( Page 105 Checking warning output (Process alarm))
• Disabled: Does not detect Process alarm.
• Enabled: Detects Process alarm.
Diagnostic
Set it to "Disabled".
alarm
HTTPS setting
Set this parameter when encrypting the communications with the Web
server. ( Page 67 HTTPS setting).
• HTTP & HTTPS concurrent operation: HTTP and HTTPS
communications are possible.
• only HTTPS; no HTTP: Only HTTPS communications are possible.
Output
Set the output operation when a fieldbus error occurs.
behaviour on
• All outputs off: All outputs are turned off.
fieldbus error
• Enable substitute value: Output is produced according to the
substitute value of the output module.
• Hold last value: The output status is maintained.
Module
Set the I/O module operation during Hot swap.
behaviour on
• Continue data exchange: The operation of the output module is
hot swap
maintained.
• Behaviour like on fieldbus error: The output module is operated
according to the setting of Output behaviour on fieldbus error.
Data format
Set how to send communication data.
• Motorola: Communication data is sent in big-endian format.
• Intel: Communication data is sent in little-endian format.
The data format of the RJ71GN11-T2 is little endian, so fix it to "Intel".
Precautions
"IP address" and "IP address USB port" cannot be set to the same value. Also, do not set the same value for the network part
of the IP address (1st to 3rd octets when the subnet mask is set to 255.255.255.0).
7 NZ2FT-GN
112
7.6 Parameter Setting
Setting range
Default
• 192.168.1.202
192.168.1.202
• 192.168.2.202
• 192.168.3.202
• 192.168.4.202
• 192.168.5.202
0.0.0.1 to
192.168.0.202
223.255.255.254
128.0.0.0 to
255.255.255.0
255.255.255.248
• Disabled
Enabled
• Enabled
• Disabled
Disabled
• Enabled
• Disabled
Disabled
• Enabled
• HTTP & HTTPS
HTTP &
concurrent operation
HTTPS
• only HTTPS; no HTTP
concurrent
operation
• All outputs off
All outputs off
• Enable substitute value
• Hold last value
• Continue data
Continue
exchange
dataexchange
• Behaviour like on
fieldbus error
• Motorola
Intel
• Intel
Web
GX
server
Works3