Malfunctions
Error
Meaning
channel
m = module
number 1
Error number 0, no error or end of a message status
–
–
Error number 10, upper limit value exceeded;
Depending on the parameterisation, the module reports the error when monitoring is activated.
Input signals will, however, still be processed.
Em.0
Upper flow rate limit
value exceeded
Em.2
Upper pressure limit
value exceeded
Em.3
Upper pressure
change limit value
exceeded
Error number 15, module/channel failed;
All electrical module functions are stopped.
Em.0
Flow sensor defec-
tive
Em.2
Pressure sensor
defective
76
Remedy
–
– Check flow.
– Check parameterised limit value.
– If necessary, adjust the diagnostics
limit values startup parameter.
– Check pressure.
– Check parameterised limit value.
– If necessary, adjust the diagnostics
limit values startup parameter.
– Check pressure change.
– Check parameterised limit value.
– If necessary, adjust the diagnostics
limit values startup parameter.
– Check system for leakage.
– Power off/on necessary.
– If this error occurs again, replace
device.
– Check whether the input pressure is
too high.
– Power off/on necessary.
– If this error occurs again, replace
device.
Enable parameter
Cannot be deacti-
vated
Monitoring: 4828 +
m * 64 + 0, bit
6, monitoring limit
values è Tab. 53
Upper pressure limit
value module param-
eter.
Cannot be deacti-
vated
Festo — MSE6-E2M — 2022-08d