Festo MSE6-E2M Operating Instruction page 25

Energy efficiency module
Table of Contents

Advertisement

Functions
5.2.2.4
Input word Em.2 pressure P2
In the input word Em.0, the pressure value P2 is displayed in accordance with the parameterised
pressure unit. The presetting of the module parameter "Unit pressure" is "mbar".
Data format of input word sign + 15 bits, right-justified
D15
D14
D13 D12 D11 D10 D9
VZ
B14
B13 B12 B11 B10 B9
MSB
Abbreviations used
VZ
Sign, for data format sign + 15 bit, always=0, positive value
B0 ... B14
Pressure value P2
DO ... D15
16-bit input data field
MSB/LSB
Most significant bit/least significant bit
Tab. 8: Data format of input word Em.2 "Pressure P2"
Pressure P2
[bar]
0
1
4
...
7.36
...
14
Tab. 9: Unit-dependent pressure values
The pressure measurement data is presented according to the unit and is rounded off.
Measured value resolution:
• kPa: 2
• mbar: 20
• psi/10: 5
5.2.2.5
Input word Em.5 pressure change DP2
The pressure change value is transmitted exclusively as a selectable input word, Em.5. The output
word, Am.1, input address must in this case have the value 0. The pressure change value is specified
in the data format sign + 15 bits.
Depending on the parameterised pressure unit and the parameterised measurement interval, the
pressure change is sent to the higher-order controller as the input word, 2 bytes, 16 bits. The pressure
change value is stored in the input word as follows.
Festo — MSE6-E2M — 2022-08d
D8
B8
Input value
[kPa]
0
100
400
...
736
...
1400
D7
D6
D5
D4
B7
B6
B5
B4
[mbar]
0
1000
4000
...
7360
...
14000
D3
D2
D1
D0
B3
B2
B1
B0
LSB
[psi/10]
0
145
580
...
1067
...
2030
25