Connecting To The Network - Festo MSE6-E2M Operating Instruction

Energy efficiency module
Table of Contents

Advertisement

Commissioning
Network-specific LEDs
MS
Module status, red, green
NS
Network status, red, green
TP1
Link/Traffic 1, green
TP2
Link/Traffic 2, green
1) In the standard operating status all green LEDs are on. The yellow and red LEDs are not on
2) The LED NS is off if there is no network connection
3) Parameterisation modified or force active
Tab. 26: LED displays
8.4.2

Connecting to the network

Connection technology
The network is connected at the bus node CPX-FB36 with the following connection technology:
Connection technology
2 sockets, M12, D-coded, 4-pin, according to
IEC 61076-2
Tab. 27: Overview of connection technology and network plug connectors
The NECU-M-S-D12G4-C2-ET plug is designed for Ethernet cables with a diameter of 6 ... 8 mm.
Network connections
The network connections are marked with X1 and X2.
Connection X1
Tab. 28: Pin allocation connection X1, EtherNet/IP
Connection X2
44
2)
Pin
Signal
1
TD+
2
RD+
3
TD–
4
RD–
Housing
Shield/FE
Pin
Signal
1
RD+
2
TD+
3
RD–
1)
CPX-specific LEDs
PS
Power system, green
PL
Power load, green
SF
System failure, red
M
Modify, yellow
Network connectors
NECU-M-S-D12G4-C2-ET plug
Explanation
Transmit Data, TD+
Receive Data, RD +
Transmitted data –
Received data –
Shield/functional earth
Explanation
Receive Data, RD +
Transmit Data, TD+
Received data –
Festo — MSE6-E2M — 2022-08d
3)

Advertisement

Table of Contents
loading