Commissioning
1
2
Fig. 22: DIL switches on bus node CPX-M-FB13
Setting the operating mode with DIL switch 1
The energy efficiency module only supports the Remote I/O operating mode with the bus node
CPX-FB13, factory setting.
All switch elements of the DIL switch 1 must be in the OFF position.
DIL switch 1
DIL 1.1: OFF
DIL 1.2: OFF
Factory setting
DIL 1.1: ON
DIL 1.2: OFF
DIL 1.1: OFF
DIL 1.2: ON
DIL 1.1: ON
DIL 1.2: ON
Tab. 22: Setting the operating mode with DIL switch 1
DIL switch 2
All switch elements of DIL switch 2 must be in the OFF position, factory setting.
Setting station number and diagnostic mode, DIL switch 3
Station numbers may only be assigned once per controller.
Festo — MSE6-E2M — 2022-08d
1
2
3
4
3
4
Description
Remote I/O operating mode
All the functions of the energy efficiency module are controlled
directly by the PROFIBUS master.
Not supported by the energy efficiency module.
DIL switch elements 1.1 and 1.2 must be in the OFF position.
DIL switch 1: operating mode
DIL switch 2: Reserved
DIL switch 3, element 8: diagnostic mode
DIL switch 3, element 1... 7: station number
39