Festo MSE6-E2M Operating Instruction page 64

Energy efficiency module
Table of Contents

Advertisement

Parameterisation
Module parameter: unit consumption
Function number
4828 + m * 64 + 8
Description
Specifies the unit for all consumption-related data.
Bit
Bit 4, 5: unit consumption
All other bits are reserved.
Bit
5 4
Value
0 0
0
0 1
1
1 0
2
1 1
3
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN29 è 10.2 Error numbers.
Tab. 49: Unit consumption module parameter
Module parameter: unit flow standard
Function number
4828 + m * 64 + 8
Description
Sets the flow rate standard for all flow-related and consumption-related data.
Bit
Bit 6, 7: flow rate standard
All other bits are reserved.
Bit
7 6
Value
0 0
0
0 1
1
1 0
2
1 1
3
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN29 è 10.2 Error numbers.
Tab. 50: Flow rate standard module parameter
Pressure change sample time module parameter
The parameter specifies the time of the measuring interval, during which the pressure values for the
calculation of the pressure change are determined. The set time corresponds to the parameterised
value, multiplied by 100 ms. The data width is 8 bits, 1 byte.
64
m = module number 1
Meaning
l, default
scf
Not permissible
m = module number 1
Meaning
DIN 1343, default
ISO 2533
ISO 6358
Not permissible
Festo — MSE6-E2M — 2022-08d