Festo MSE6-E2M Operating Instruction page 65

Energy efficiency module
Table of Contents

Advertisement

Parameterisation
Module parameter: pressure change sample time
Function number
4828 + m * 64 + 10
Description
Specifies the time interval between two pressure measurements, from whose
measured values the pressure change is calculated.
Bit
Bit 0 ... 8: Time interval between 2 measurements
Values
1 ... 255
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN29 è 10.2 Error numbers.
Tab. 51: Pressure change sample time module parameter
Critical limits module parameter
The limit values module parameter can be used to specify the specific upper limit value pressure,
upper limit value flow rate and upper limit value pressure change limit values. The data width is 16
bits, 2 bytes.
If the unit is changed, the data for the critical limits is not changed and may need to be adjusted
separately.
Module parameter: upper limit value flow rate
Function number
4828 + m * 64 + 11 (low byte)
4828 + m * 64 + 12 (high byte)
Description
An upper flow limit value can be set for the module.
Values
2-byte value: low byte + 256 * high byte
Default: 32767, low byte = 255; high byte = 127
Permissible values: 0 ... 32767
Comment
If parameter monitoring is active, Pm.0.7, invalid values will result in parameter-
isation error FN29 è 10.2 Error numbers.
If the flow rate set according to the parameterised unit exceeds the parameter-
ised upper limit value, the diagnostic message FN10 is output if the monitor
limit values parameter is active.
The monitoring of limit value violation only becomes active after the expiry of
the time set in the monitor critical limit values parameter startup. The time is
active even after shifting to the pressurise state.
Tab. 52: Upper limit value flow rate module parameter
Festo — MSE6-E2M — 2022-08d
m = module number 1
100, default ... 25500 ms
m = module number 1
65