2
Installation as function module F24
2.4.2
Arrangement of the DIL switches
There are 5 DIL switches available for configuring the bus node. They are located underneath the DIL
switch cover (è Section 2.4.1).
1
DIL switch 1:
– Operating mode and baud rate
2
DIL switch 1 and 2:
– Baud rate
3
DIL switch 3:
– Function F24/F23
– CC-Link slave address
4
DIL switch 4:
– Mapping optimisation
5
DIL switch 5:
– HOLD/CLEAR
– System diagnostics
Fig. 2.3
DIL switches in the bus node CPX-FB23-24 – function module F24
(additional information è Sections 2.4.4 ... 2.4.10)
2.4.3
Setting the DIL switches
1. Switch off the power supply.
2. Remove the DIL switch cover (è Section 2.4.1).
3. Carry out the required settings (è Section 2.4.4 ... 2.4.10).
4. Attach the DIL switch cover again (è Section 2.4.1).
Note
Parameterisation via DIL switch settings is taken over only when the power supply is
switched on.
14
1
2
3
4
5
Festo – P.BE-CPX-FB23-24-EN – 1411b – English
ON
ON
1
2
1
2
ON
ON
1
2
1
2