DEFINED CONTENTS OF AUXILIARY OUTPUTS 1-4

No.
Items
0
Not Used
1
Common Alarm
2
Energize to Stop
3
Idle Control
4
Preheat Control
5
Gen Close Output
6
Mains Close Output
7
Open Breaker
8
Rise Speed
9
Drop Speed
10
Generator Run
11
Fuel Pump Control
12
High Speed Control
13
In Auto Mode
14
Shutdown Alarm
15
Audible Alarm
16
Heater Control
17
Fuel Output
18
Crank Output
19
ECU Stop
20
ECU Power
21
ECU Warn
22
ECU Shutdown
23
ECU Comm. Failure
HGM6100LT Series Genset Controller User Manual
Table 8 – Defined Contents of Auxiliary Outputs 1-4
Output is disabled when this item is selected.
Including all shutdown alarm and warning alarm. When a warning
alarm occurs, the alarm won't self-latch; When a shutdown alarm
occurs, the alarm will self-latch until alarm is reset.
Used for the genset with stop solenoid. Pick-up when idle speed is
over while disconnect when ETS delay is over.
Used for the genset with idle speed. Pick-up when crank while
disconnect when enter into warming up. Pick-up when stop idle
while disconnect when genset stop completely.
Close before started and disconnect before powered on.
When close time is set as 0, it is continuous closing.
HGM6110LT without.
When close time is set as 0, open breaker is disabled.
Pick-up when enter into warming up time. Disconnect when raise
speed auxiliary input active.
Pick-up when enter into stop idle or ETS solenoid stop (shutdown
alarm). Disconnect when drop speed auxiliary input active.
Output when genset is in normal running, disconnect when
rotating speed is lower than engine speed after fired.
Pick-up when the fuel level lower than the open threshold or low
fuel level warning is active; disconnect when the fuel level over the
close threshold and the low fuel level warning input is disabled.
Output when it enters into warming up time, and disconnect after
cooling.
The controller is in Auto Mode.
Output when shutdown alarm occurs and open when alarm resets.
When shutdown alarm and warn alarm occur, audible alarm is set
as 300s. In audible alarm output duration, when panel any key or
"alarm mute" input is active, it can remove the alarm.
It is controlled by heater of temperature sensor's limited threshold.
Action when genset is starting and disconnect when stop is
completed.
Genset output in start output status and open in other status.
Used for ECU engine and control its stop.
Used for ECU engine and control its power.
Indicate ECU sends a warning signal.
Indicate ECU sends a shutdown signal.
Indicate controller not communicates with ECU.