No.
Function
30
Generator N2 Input
Mains
R
phase
31
Sensing Input
Mains
S
phase
32
Sensing Input
Mains
T
phase
33
Sensing Input
34
Mains N1 Input
35
RS485 Common Ground
36
RS485-
37
RS485+
38
Aux. Input 4
39
Aux. Input 5
40
Sensor COM
41
CAN COM
42
CAN L
43
CAN H
44
NULL
NOTE 1: USB port in controller rear panel is configurable parameter port; user can directly program via PC.
NOTE 2: ETHERNET port in controller rear panel is network monitoring port; user can directly program via PC.
HGM6100LT Series Genset Controller User Manual
Cable Size
1.0mm
2
Connect to generator N-wire.
Voltage
Connect to mains R phase (2A fuse is recommended)
2
1.0mm
(HGM6110LT without.)
Voltage
Connect to mains S phase (2A fuse is recommended)
1.0mm
2
(HGM6110LT without.)
Voltage
Connect to mains T phase, (2A fuse is recommended)
1.0mm
2
(HGM6110LT without.)
1.0mm
2
Connect to mains N-wire. (HGM6110LT without.)
/
Impedance-120Ω shielding wire is recommended, its
2
0.5mm
single-end connect with ground.
2
0.5mm
1.0mm
2
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
1.0mm
2
Sensor common port.
2
0.5mm
Impedance-120Ω shielding wire is recommended, its
2
0.5mm
single-end connects with ground (connect this port to
engine ECU if engine type is not "conventional engine").
0.5mm
2
Description