No.
Items
19(14)
Switch Close Time
20(15)
Flywheel Teeth
21(16)
Gen Abnormal Delay
Gen Over Voltage
22(17)
Shutdown
Gen Under Voltage
23(18)
Shutdown
Gen
Under
24(19)
Shutdown
Gen
Over
25(20)
Shutdown
Gen Under Frequency
26(21)
Shutdown
Gen Over Frequency
27(22)
Shutdown
High
Temperature
28(23)
Shutdown
Low
Oil
29(24)
Shutdown
30(25)
Low
Fuel
HGM6100LT Series Genset Controller User Manual
Range
(0.0-10.0)s
(10.0-300.0)
(0-20.0)s
(30-60000)V
(30-60000)V
Speed
(0-6000)r/min 1200
Speed
(0-6000)r/min 1710
(0-75.0)Hz
(0-75.0)Hz
(80-300)ºC
Pressure
(0-400)kPa
Level (0-100)%
Default
0, it is from end of ETS solenoid delay to
genset at rest.
Mains' or generator's switch closing pulse
5.0
width, when it is 0, output is continuous.
Number of flywheel teeth, it can detect
118
disconnection conditions and engine speed.
10.0
Over or under voltage alarm delay.
When genset voltage is over the point,
generator over voltage is active. When the
264
point is 60000V, generator over voltage is
disabled.
When generator voltage is under the point,
generator under voltage is active. When the
196
point is 30V, generator under voltage is
disabled.
When the engine speed is under the point for
10s, shutdown alarm signal is sent out.
When the engine speed is over the point for
2s, shutdown alarm signal is sent.
When generator frequency is lower than the
45.0
point (not equal to 0) for 10s, shutdown
alarm signal is sent.
When generator's frequency is over the point
57.0
and continues for 2s, generator over
frequency is active.
When
external
sensor value is over this point, it sends out
high temp. alarm. This value is only judged
for external connected temp. sensor after
98
safety on time is over. When the value is 300,
warning alarm won't be sent. (only suited for
temperature sensor, except for high temp.
alarm signal inputted by programmable input
port.)
When external connected oil pressure sensor
value is under this point, low oil pressure
delay is started (judged after safety on time
103
is over). When the value is 0, warning alarm
won't be sent. (only suited for oil pressure
sensor, except for low oil pressure alarm
signal inputted by programmable input port.)
10
When fuel level sensor value under this point
Description
connected
temperature