PROTECTION

5.1

WARNING

When controller detects the warning signal, genset only sends alarm and not stop. The alarms are
displayed in LCD.
No.
Warning
1
Loss of Speed Signal
2
Gen Over Current
3
Failed to Stop
4
Low Fuel Level
5
Failed to Charge
6
Battery Under Voltage
7
Battery Over Voltage
8
Low Coolant Level
9
Temp. Sensor Open
10
OP Sensor Open
11
Maintenance Due
12
High Temp.
13
Low Oil Pressure
HGM6100LT Series Genset Controller User Manual
Table 4 – Warning Alarms
When the speed of genset is 0 and speed loss delay is 0, controller will
send warning alarm signal and it will be displayed in LCD.
When the current of genset is higher than threshold (definite time) and
setting over current delay is 0, controller will send warning alarm signal
and it will be displayed in LCD.
When genset cannot stop after the "ETS delay/fail to stop delay" is over,
controller will send warning alarm signal and it will be displayed in LCD.
When the fuel level of genset is lower than threshold or low fuel level
warning is active, controller will send warning alarm signal and it will be
displayed in LCD.
When the voltage of genset charger is lower than threshold, controller
will send warning alarm signal and it will be displayed in LCD.
When the battery voltage of genset is lower than threshold, controller will
send warning alarm signal and it will be displayed in LCD.
When the battery voltage of genset is higher than threshold, controller
will send warning alarm signal and it will be displayed in LCD.
When low coolant level input is active, controller will send warning alarm
signal and it will be displayed in LCD.
When sensor hasn't connected to corresponding port, controller will
send warning alarm signal and it will be displayed in LCD.
When sensor hasn't connected to corresponding port, controller will
send warning alarm signal and it will be displayed in LCD.
Maintenance type is running time. When genset running time is longer
than maintenance time of user setting or the maintenance type is date,
the current date is over the set value, and the maintenance action is set
as warn, controller send warning alarm signal and it will be displayed in
LCD.
When the water/cylinder temperature of genset is higher than threshold
and Enabled High Temp. Stop Inhibited or Input High Temp. Stop
Inhibited is active, controller will send warning alarm signal and it will be
displayed in LCD.
When the oil pressure of genset is less than threshold and Enabled Low
Oil Pressure Stop Inhibited or Input Low Oil Pressure Stop Inhibited is
active, controller will send warning alarm signal and it will be displayed
in LCD.