Defined Contents Of Auxilary Output 1-4; Defined Contents Table Of Auxilary Output 1-4 - Smartgen HGMS62 User Manual

Table of Contents

Advertisement

8.2

DEFINED CONTENTS OF AUXILARY OUTPUT 1-4

8.2.1

DEFINED CONTENTS TABLE OF AUXILARY OUTPUT 1-4

No.
Type
0
Not Used
1
Custom Period Output 1
2
Custom Period Output 2
3
Custom Period Output 3
4
Custom Period Output 4
5
Custom Period Output 5
6
Custom Period Output 6
Custom
7
Output 1
Custom
8
Output 2
Custom
9
Output 3
Custom
10
Output 4
Custom
11
Output 5
Custom
12
Output 6
13
Reserved
14
Reserved
15
Reserved
16
Reserved
17
Air Flap Control
18
Audible Alarm
Louver Control
19
20
Fuel Pump Control
21
Heater Control
22
Cooler Control
23
Pre-fuel Output
24
Excitation Output
HGMS62 Split Type Genset Controller User Manual
Table 14 – Defined Contents of Auxiliary Output 1-4
Combination
Combination
Function description refers to the following contents.
Combination
Combination
Combination
Combination
Action in over speed shutdown and emergency shutdown, it can
close engine inlet port.
Action in warning, shutdown, ELE trip. It can connect an alarm
externally. When "Alarm Mute" is active, its output is inhibited.
Action in genset starts, it disconnects after genset stops
completely.
Its action is controlled by fuel pump threshold of level sensor.
Its action is controlled by heating control threshold of temp
sensor.
Its action is controlled by cooling control threshold of temp
sensor.
Action in crank-safety running.
Outputs in crank process, if there is no gen frequency in high
speed running, it outputs 2s again.
Function Description
Page 36 of 58

Advertisement

Table of Contents
loading

Table of Contents