13.7 CUMMINS QSZ13
Terminals of controller
Programmable output 1
Starting relay output
Programmable output 2
Programmable output 3
CAN_SCR
CAN(H)
CAN(L)
Engine type: Common J1939.
13.8 DETROIT DIESEL DDEC III / IV
Terminals of controller
Programmable output 1
Starting relay output
CAN_SCR
CAN(H)
CAN(L)
Engine type: common J1939.
HGM6100LT Series Genset Controller User Manual
Table 24 – Engine OEM Connector
OEM connector of engine
45
-
16&41
19&41
-
1
21
Table 25 – Engine CAN Port
CAN port of engine
Expand 30A relay, battery
voltage
is
supplied
relay.
-
-
CAN(H)
CAN(L)
Connect to starter coil directly.
Setting to idle speed control, normally
open output. Making 16 connect to 41
during high-speed running of controller via
external expansion relay.
Setting to pulse raise speed control,
normally open output. Making 19 connect
with 41 for 0.1s during high-speed
warming
of
controller
expansion relay.
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Set programmable output 1 as "Fuel
by
Output".
Connect to starter coil directly.
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
via
external
Remark
Page 44 of 50