Advertisement

NOTE: a. Icom must connect to battery cathode of the controller.
b. When there is load current, open circuit is inhibited in the CT secondary side.
5) Withstand Voltage Test
When the controller has been installed in the control panel, during the test please disconnect all
the terminals, in case high voltage damages the controller.
HGM6100LT Series Genset Controller User Manual
Page 40 of 50