Sensor Selection - Smartgen HGM6100LT Series User Manual

Genset controller
Hide thumbs Also See for HGM6100LT Series:
Table of Contents

Advertisement

7.4

SENSOR SELECTION

No.
Items
Temperature
1
Sensor
Pressure
2
Sensor
Fuel Level
3
Sensor
NOTE: It needs special instructions for ordering when the genset uses (4-20)mA or (0-5)V sensor.
HGM6100LT Series Genset Controller User Manual
Table 10 – Sensors Selection
Content
0 Not used
1 User Configured (Resistance Type)
2 VDO
3 SGH
4SGD
5 CURTIS
6 DATCON
7 VOLVO-EC
8 SGX
9 User Configured (4-20)mA
10 User Configured (0-5)V
11 Digital Closed
12 Digital Open
13 Reserved
14 Reserved
0 Not used
1 User Configured (Resistance Type)
2 VDO 10Bar
3 SGH
4 SGD
5 CURTIS
6 DATCON 10Bar
7 VOLVO-EC
8 SGX
9 User Configured (4-20)mA
10 User Configured (0-5)V
11 Digital Closed
12 Digital Open
13 VDO 5Bar
14 Reserved
0 Not used
1 User Configured (Resistance Type)
2 SGH
3 SGD
4 User Configured (4-20)mA
5 User Configured (0-5)V
6 Digital Closed
7 Digital Open
Description
Defined input resistance range is
0Ω~6000Ω, factory default is SGD
sensor.
Defined input resistance range is
0Ω~6000Ω, factory default is SGD
sensor.
Defined input resistance range is
0Ω~6000Ω, factory default is SGD
sensor.