13.19 YUCHAI
It is suitable for Yuchai BOSCH common rail electronic-controlled engine.
Terminals of controller
Programmable output 1
Starting relay output
CAN_SCR
CAN(H)
CAN(L)
Battery
Battery negative
Battery positive
Engine type: BOSCH.
13.20 WEICHAI
It is suitable for Weichai BOSCH common rail electronic-controlled engine.
Terminals of controller
Programmable output 1
Starting relay output
CAN_SCR
CAN(H)
CAN(L)
Engine type: GTSC1.
NOTE: If there is any question of connection between controller and ECU communication, please feel free to contact
SmartGen service.
HGM6100LT Series Genset Controller User Manual
Table 39 – Engine 42 Pins Port
Engine 42 pins port
1.40
-
-
1.35
1.34
Table 40 – Engine 2 Pins Port
Engine 2 pins port
1
2
Table 41 – Engine Port
Engine port
1.40
1.61
-
1.35
1.34
Remark
Set programmable output 1 as "Fuel
Output";
Connect to engine ignition lock.
Connect to starter coil directly.
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
2
Wire diameter 2.5mm
Wire diameter 2.5mm
2
Remark
Set programmable output 1 as "Fuel
Output";
Connect to engine ignition lock.
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
.
.
Page 49 of 50