Smartgen HGM6100LT Series User Manual page 24

Genset controller
Hide thumbs Also See for HGM6100LT Series:
Table of Contents

Advertisement

No.
Items
48(43)
Aux. Input 2 Set
49(44)
Aux. Input 2 Active
50(45)
Aux. Input 2 Delay
51(46)
Aux. Input 3 Set
52(47)
Aux. Input 3 Active
53(48)
Aux. Input 3 Delay
54(49)
Aux. Input 4 Set
55(50)
Aux. Input 4 Active
56(51)
Aux. Input 4 Delay
57(52)
Aux. Input 5 Set
58(53)
Aux. Input 5 Active
59(54)
Aux. Input 5 Delay
60(55)
Power On Mode
61(56)
Module Address
62(57)
Password
Crank
Disconnect
63(58)
Condition
Engine
Speed
64(59)
Crank Disconnect
Frequency of Crank
65(60)
Disconnect
Oil Pressure of Crank
66(61)
Disconnect
High
Temp.
67(62)
Inhibit
68(63)
Low OP Shut Inhibit
69(64)
AC System
Temp. Sensor Curve
70(65)
Type
Pressure
71(66)
Curve Type
Fuel
Level
72(67)
Curve Type
HGM6100LT Series Genset Controller User Manual
Range
(0-23)
(0-1)
(0-20.0)s
(0-23)
(0-1)
(0-20.0)s
(0-23)
(0-1)
(0-20.0)s
(0-23)
(0-1)
(0-20.0)s
(0-2)
(1-254)
(0-9999)
(0-6)
of
(0-3000)r/min 360
(0.0-30.0)Hz
(0-400)kPa
Shut
(0-1)
(0-1)
(0-3)
(0-14)
Sensor
(0-14)
Sensor
(0-7)
Default
Factory default: Low oil pressure shutdown.
2
See table 9.
0
Factory default: close.
2.0
10
Factory default: Remote start. See table 9.
0
Factory default: close to activate.
2.0
Factory default: Low fuel level warn. See
11
table 9.
0
Factory default: close.
2.0
Factory default: Low coolant level warn. See
12
table 9.
0
Factory default: close.
2.0
0
0: Stop Mode; 1: Manual Mode; 2: Auto Mode
1
The communication address of controller.
0318
See
.
NOTE 5
Conditions
(generator
sensor, oil pressure), Each condition can be
2
used alone and simultaneously to separating
the start motor and engine as soon as
possible.
When engine speed is over this point, starter
will disconnect.
When generator frequency is over this point,
14.0
starter will disconnect.
When the oil pressure is over this point,
200
starter will disconnect.
Default: when temperature is too high, the
0
genset alarms and shuts down. See
Default: when oil pressure is too low, it
0
alarms and shuts down. See
0: 3P4W 1: 2P3W
0
2: 1P2W 3: 3P3W
4
SGD. See table 10.
4
SGD. See table 10.
3
SGD. See table 10.
Description
of
disconnecting
frequency,
magnetic
.
NOTE4
Page 24 of 50
starter
pickup
.
NOTE3