Terminals of controller
CAN_SCR
CAN(H)
CAN(L)
Engine type: Volvo.
NOTE: When this engine type is selected, preheating time should be set to at least 3 seconds.
13.17 VOLVO EDC4
Suitable engine types are TD520, TAD520 (optional), TD720, TAD720 (optional), TAD721, TAD722, and
TAD732.
Terminals of controller
Programmable output 1
Starting relay output
CAN_SCR
CAN(H)
CAN(L)
Engine type: Volvo EDC4.
13.18 VOLVO-EMS2
Volvo Engine types are TAD734, TAD940, TAD941, TAD1640, TAD1641, and TAD1642.
Terminals of controller
Programmable output 1
Programmable output 2
CAN_SCR
CAN(H)
CAN(L)
Engine type: Volvo-EMS2.
NOTE: When this engine type is selected, preheating time should be set to at least 3 seconds.
HGM6100LT Series Genset Controller User Manual
Table 36 – "Data bus" Connector
"Data bus" connector
-
1
2
Table 37 – Connector
Connector
Expanded 30A relay, and
relay
offers
battery
voltage to terminal 14.
Fuse is 16A.
-
1
-
12
13
Table 38 – Engine CAN Port
Engine's CAN port
6
5
3
4
-
1(Hi)
2(Lo)
Remark
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
Set programmable output 1 as "Fuel
Output".
Connect to starter coil directly.
Connected to negative of battery.
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Remark
ECU stop;
Programmable output 1 "ECU stop".
ECU power;
Programmable output 2 "ECU power".
Negative power.
Positive power.
CAN communication shielding line.
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Page 48 of 50