No.
Items
73(68)
Generator Poles
Temp. Sensor Open
74(69)
Circuit Action
Oil Pressure Sensor
75(70)
Open Circuit Action
Disconnect
76(71)
Pressure Delay
77(72)
Scheduled Run
78(73)
Cycle Setting
79(74)
Auto Start Inhibit
80(75)
Cycle Setting
81(76)
Over Power
82(77)
Start Interface
Maintenance
83(78)
Password
84(79)
Date/Time
Flexible Sensor Curve
85(80)
Type
86(81)
Engine Type
87(82)
SPN Alarm Version
88(83)
Custom Theme
89(84)
Fuel Output Time
HGM6100LT Series Genset Controller User Manual
Range
Default
(2-64)
4
(0-2)
1
(0-2)
1
Oil
(0-20.0)s
0.0
(0-1)
0
(0-2)
0
(0-1)
0
(0-2)
0
(0-2)
0
(0-1)
0
(0-9999)
0
Set the date/time of controller.
(0-2)
0
(0-39)
0
(0-3)
0
(0-2)
0
(1-60)s
1
Description
Number
of
magnetic
calculating speed of engine without speed
sensor.
0: Not used; 1: Warn; 2: Shutdown
When disconnect conditions include oil
pressure and engine oil pressure is higher
than disconnect oil pressure delay, the
genset is regarded as start successfully and
starter will disconnect.
0: Disabled; 1: Enabled.
Circulate condition: monthly, weekly and
daily can be selected.
Start time and duration can be set.
0: Disabled; 1: Enabled.
Circulate condition: monthly, weekly and
daily can be selected.
Don't start time and duration can be set.
0: Not used; 1: Warn; 2: Shutdown
When power is higher than preset value and
duration exceeds than delay, over power
warning is active. Return and delay value can
be set.
0: Disabled; 1: Enabled。
Start interface delay can be set.
Enter password interface of maintenance
configuration.
0: User-defined temperature sensor
1: User-defined pressure sensor
2: User-defined level sensor
Choose sensor which need to be set, input
every point (8 points need to be input)
resistance and corresponding value (or
current, voltage) of curve.
0: Conventional Engine.
SPN Alarm Version.
0: Default Theme; 1: OEM Plant Theme;
2: Terminal User Theme
It is the time of the genset fuel output during
poles,
used for
Page 25 of 50