Smartgen HGM6100LT Series User Manual page 16

Genset controller
Hide thumbs Also See for HGM6100LT Series:
Table of Contents

Advertisement

No.
Items
19
Input Shutdown
20
Over Power
21
ECU Shutdown
22
ECU Comm. Failure
23
Short-circuit Shutdown
User
Configured
24
Shutdown
User
Configured
25
Shutdown
User
Configured
26
Shutdown
User
Configured
27
Shutdown
HGM6100LT Series Genset Controller User Manual
than maintenance time of user setting or the maintenance type is date,
the current date is over the set value, and maintenance action is set as
shutdown, controller send shutdown alarm signal and it will be displayed
in LCD. Maintenance alarm can be reset by setting maintenance
parameters with password.
When external input is active, controller will send shutdown alarm signal
and it will be displayed in LCD.
If over power detection is enabled, when the controller detects that the
over power value (power is positive) has exceeded the pre-set value and
the action selects "Shutdown", it will initiate a shutdown alarm.
If an error message is received from ECU via J1939, it will initiate a
shutdown alarm.
If the module does not detect the ECU data, it will initiate a shutdown
alarm.
When short-circuit signal is enabled, and the short-circuit action selects
"Shutdown Alarm", controller will initiate a shutdown alarm signal after
meeting the short-circuit requirements.
When controller detects that the input port 1 selects 33 "User
Configured", close/open is active and the action selects "Shutdown
Alarm", when the controller meets the selection of active range (not
1
inactive), the controller will initiate a shutdown alarm signal, and the
LCD will display the "User Configured 1 Shutdown".
When controller detects that the input port 2 selects 33 "User
Configured", close/open is active and the action selects "Shutdown
Alarm", when the controller meets the selection of active range (not
2
inactive), the controller will initiate a shutdown alarm signal, and the
LCD will display the "User Configured 2 Shutdown".
When controller detects that the input port 3 selects 33 "User
Configured", close/open is active and the action selects "Shutdown
Alarm", when the controller meets the selection of active range (not
3
inactive), the controller will initiate a shutdown alarm signal, and the
LCD will display the "User Configured 3 Shutdown".
When controller detects that the input port 4 selects 33 "User
4
Configured", close/open is active and the action selects "Shutdown
Alarm", when the controller meets the selection of active range (not
Description
Page 16 of 50