Defined Contents Of Auxiliary Output Ports 1-6; Defined Contents Table Of Auxiliary Output Ports 1-6 - Smartgen HEM4000 User Manual

Engine controller
Table of Contents

Advertisement

Outlet pressure correlated setting: if flow and head are to be calculated via water pressure, one of auxiliary sensor 1-4
needs to be configured as outlet pressure sensor, and meanwhile, curve type needs to be the corresponding one. Then
set the outlet pressure correlated sensor and select the corresponding auxiliary sensor, and at this time, flow and head
can be calculated via water pressure.
If E-driven suction pump needs to judge whether it has stopped output by water pressure, outlet pressure correlation
setting is also needed.

8.2 DEFINED CONTENTS OF AUXILIARY OUTPUT PORTS 1-6

8.2.1

DEFINED CONTENTS TABLE OF AUXILIARY OUTPUT PORTS 1-6

No.
Type
0
Not Used
1
Custom Period Output 1
2
Custom Period Output 2
3
Custom Period Output 3
4
Custom Period Output 4
5
Custom Period Output 5
6
Custom Period Output 6
7
Custom Combined Output 1
8
Custom Combined Output 2
9
Custom Combined Output 3
10
Custom Combined Output 4
11
Custom Combined Output 5
12
Custom Combined Output 6
13
Reserved
14
Reserved
15
Air Flap Control
16
Audible Alarm
17
Louver Control
18
Fuel Pump Control
19
Heater Control
20
Cooler Control
21
Fuel Pre-supply Output
HEM4000 Engine Controller User Manual
Table 9 – Defined Contents of Auxiliary Outputs 1-6
Details of function description please see the following.
Act when over speed shutdown and emergence stop, and it can
close the air inflow to stop the engine sooner.
Act when warning and shutdown alarms occur, it can be
connected to annunciator externally. When auxiliary input "alarm
mute" is active or press any key on the panel, it can be stopped.
When new alarm or shutdown occurs, it will output again.
Act when engine is starting and disconnect when engine stops
completely.
It is controlled by fuel pump control threshold of level sensor.
It is controlled by heater control threshold of temperature
sensor.
It is controlled by cooler control threshold of temperature
sensor.
In standby status, when fuel pre-supply output is active, set fuel
pre-supply rest time and fuel pre-supply time are outputted
circularly. If set fuel pre-supply rest time is 0, fuel pre-supply is
Description
Page 29 of 46