Option Compatibility - YASKAWA CC-Link SI-C3 Installation Manual

Ac drive option
Hide thumbs Also See for CC-Link SI-C3:
Table of Contents

Advertisement

9 Troubleshooting
LED Status
Remote Device Addresses (Option)
Master
Station 1
L.RUN
SD
RD
L.ERR
×
TIME
LINE ×
L.RUN
SD
RD
L.ERR
×
Note:
○: ON / □: Flashing / ×: OFF / *: Either ON or OFF

Option Compatibility

You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
• You can only connect one option to a GA500 drive. Connect the option to the CN5 connector.
• Compatible communication options are different for different models. Refer to the drive manuals for more
information.
Option
*1
*1
PG-B3
, PG-X3
*1 *3 *4
PG-RT3
, PG-F3
*1
*1
DO-A3
, AO-A3
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
*4
*4
SI-W3
, SI-EM3
, SI-EM3D
*4
*4
EN3
, SI-EN3D
, SI-EP3, JOHB-
SMP3,
*1 *5
*1 *5
AI-A3
, DI-A3
*1
Not available for GA500 drives.
62
Station 2
Station 3
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
L.ERR
L.RUN
L.RUN
SD
SD
RD
RD
L.ERR
×
L.ERR
Table 9.4 Option Compatibility
*1 *3 *4
*4
, SI-
Cause
Electrical noise interference
along the cable running
between Station 2 and
Station 3. (L.RUN is
sometimes OFF)
Termination resistor not
connected (L.RUN is
sometimes OFF). (L.RUN is
sometimes OFF)
Connector
CN5-B, C
CN5-C
CN5-A, B, and C
CN5-A
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Possible Solutions
Reconnect the
communication line to the
SLD terminal on the CC-
Link Option connector.
Also make sure that all
power cables are properly
separated from
communication lines. (at
least 100 mm away)
Configure the final station
in the series with a
termination resistor.
Number of Options
Possible
*2
2
1
1
1

Advertisement

Table of Contents
loading

Table of Contents