Basic Functions
This product is a communication interface to operate, adjust, and monitor the drive as CC-
Link remote station with a PLC program. You can use cycle transmission of bit data and
word data, which enables high-speed communication at up to 10 Mbps.
This section explains the basic functions to operate using a PLC by CC-Link
communication function.
Note:
First, set the parameters to operate the drive using a PLC . Refer to
more information.

Monitor

You can monitor operation status of the drive from a PLC.
Follow the following directions to monitor.
1.
Set the monitor code to remote register RW
2.
Switch ON the RYC signal (request to execute the monitor code).
The data according to Monitor Code is stored in the buffer memory of the PLC.
Note:
For a list of monitor codes, write data drives, and setting ranges, refer to the instruction manual for the
drive the CC-Link Option is connected to.
38
Description
B : number of remote device nodes (42 max)
C : number of local nodes (26 max)
Sets the communication speed for CC-Link communication.
Change the parameter then cycle power on the drive.
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
Sets the automatic reset function for bUS [Option
Communication Errors].
0 : Disabled
1 : Enabled
Related Drive Parameters on page 34
.
W0
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Default
(Range)
0
(0 - 4)
0
(0, 1)