Minor Faults and Alarms

Code
Name
AEr
Station Address Error
Serial Comm
CALL
Transmission Error
Cycle Power to
CyPo
Active Parameters

Option LED States

How to Check for Errors on LED Lamps

A - 1000-Series
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Causes
CANopen Option is set to an
address outside the allowable
setting range.
The communications cable
wiring is incorrect.
There is a short circuit in the
communications cable or the
communications cable is not
connected.
A programming error occurred
on the controller side.
There is damage to the
communications circuitry.
The termination resistor setting
for MEMOBUS/Modbus
communications is incorrect.
Comm. Option Parameter Not
Upgraded
B - GA500, GA700, and GA800
Figure 9.1 Option LED Labels
9 Troubleshooting
Possible Solutions
Set F6-35 to an address within the
specified range.
Correct wiring errors.
• Repair the short-circuited or
disconnected portion of the cable.
• Replace the defective
communications cable.
Examine communications at start-up and
correct programming errors.
• Do a self-diagnostics check.
• If the problem continues, replace the
control board or the drive. Contact
Yaskawa or your nearest sales
representative to replace the control
board.
On the last drive in a MEMOBUS/
Modbus network, set DIP switch S2 to
the ON position to enable the termination
resistor.
Re-energize the drive to update the
communication option parameters.
Note:
If the option software version is not
compatible or if you install an
incorrect option to the drive, it will
trigger an alarm.
57