Minor Faults And Alarms; Option Compatibility - YASKAWA SI-B3 Installation & Technical Manual

Hide thumbs Also See for SI-B3:
Table of Contents

Advertisement

Code
Name
Option Card Fault
oFA01
(CN5-A)
oFA03,
Option Card Error
oFA04
(CN5-A)
oFA30 to
Option Card
oFA43
Connection Error
(CN5-A)
Option Not
oFb00
Compatible with Port
oFb02
Option Fault
Option Not
oFC00
Compatible with Port
or Option Fault (CN5-
C)
oFC02
Option Fault

Minor Faults and Alarms

Code
Name
Cycle Power to
CyPo
Active Parameters

Option Compatibility

You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
• You can connect two options to an FP605 drive. Connect the communication option to the CN5-A connector.
YASKAWA TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
Causes
The option connected to option
port CN5-A was changed during
run.
A fault occurred in the option.
A fault occurred in the option.
The option connected to
connector CN5-B is not
compatible.
An option of the same type is
already installed in option port
CN5-A, CN5-B, or CN5-C.
The option connected to
connector CN5-C is not
compatible.
An option of the same type is
already installed in option port
CN5-A, CN5-B, or CN5-C.
Causes
Comm. Option Parameter Not
Upgraded
9 Troubleshooting
Possible Solutions
1.
De-energize the drive.
2.
Connect the option to the correct
option port.
1.
De-energize the drive.
2.
Make sure that the option is
correctly connected to the connector.
3.
If the problem continues, replace the
option.
1.
De-energize the drive.
2.
Make sure that the option is
correctly connected to the connector.
3.
If the problem continues, replace the
option.
Connect the option to the correct
connector.
• Use connector CN5-A when you
connect the option.
To use other options, refer to those
option manuals.
Connect the option to the correct option
port.
Connect the option to the correct
connector.
• Use connector CN5-A when you
connect the option.
To use other options, refer to those
option manuals.
Connect the option to the correct option
port.
Possible Solutions
Re-energize the drive to update the
communication option parameters.
55