8 CC-Link Data List
Signal
Name
RY1A
Fault Reset
RY1B -
Reserved
1F
Note:
1.
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. You can
write the EEPROM to the drive a maximum of 100,000 times. Do not use this write command frequently.
2.
Although RYE and RYF are triggered by the rising edge of the signal, they are otherwise enabled
depending on the value that is input.
Drive → PLC
Signal
Name
RX0
Forward Run
RX1
During Reverse
1000-Series:
Terminal M1-M2
Function
GA700, GA800:
Multi-Function
RX2
Digital Output 1
Function
GA500: Terminal
MA/MB-MC
Function
RX3
Speed Agree
During Stall
RX4
Prevention
During Uv
RX5
[Undervoltage]
1000-Series, GA500:
Terminal P1
*1
Function
RX6
GA700, GA800:
Multi-Function
44
Resets a drive fault
Table 8.2 Remote I/O List (Drive → PLC)
ON: Forward Run Command Present (includes DC
Injection Braking)
OFF: No Forward Run Command
ON: During Reverse
OFF: No Reverse Run Command (includes DC
Injection Braking)
Multi-function output: H2-01
ON: Output frequency is between frequency reference
and the detection width set to L4-02 [Speed Agree
Detection Width].
Multi-Function Output: H2-02
Description
-
Description
-
-
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Comments
(Default)
-
-
Comments
(Default)
-
-
1000-Series, GA700,
GA800: H2-01 = 0
[Term M1-M2
Function Selection =
During Run]
GA500: H2-01 = E
[Term MA/MB-MC
Function Selection =
Fault]
-
-
-
1000-Series, GA700,
GA800: H2-02 = 1
[Term M3-M4
Function Selection =
Zero Speed]