YASKAWA CC-Link SI-C3 Installation Manual page 35

Ac drive option
Hide thumbs Also See for CC-Link SI-C3:
Table of Contents

Advertisement

No.
Name
(Hex.)
b1-18
Voltage
Reference Source
(0179)
(For D1000)
F6-01
Communication
Error Selection
(03A2)
(For Drive)
F6-01
Communication
Error Selection
(03A2)
(For D1000)
F6-02
Comm External
Fault (EF0)
(03A3)
Detect
(For Drive,
D1000)
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Description
the master device to control the frequency reference of the
drive.
Selects the voltage reference input source.
0 : Keypad - RUN and STOP keys
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option
7 : Input Voltage Based Control 1
8 : Input Voltage Based Control 2
Note:
• On D1000, to use the CC-Link master device as the
voltage reference, set b1-18 = 3.
Selects drive response when the drive detects a bUS [Option
Communication Error] error during communications with the
option.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Alarm - Run at d1-04
5 : Alarm - Ramp Stop
Note:
• When you set this parameter to 3 or 4, the drive will
continue operation after it detects a fault. Separately
prepare safety protection equipment and systems, for
example fast stop switches.
• Refer to the drive manual to know if settings 4 and 5 are
available. Settings 4 and 5 are available in A1000
software versions PRG: 1021 and later.
• The setting range for 1000-Series drives is different for
different software versions. Refer to the instruction
manual of your specific drive for more information.
Selects drive response when the drive detects a bUS [Option
Communication Error] error during communications with the
option.
1 : Coast to Stop
3 : Alarm Only
Selects the conditions at which EF0 [Option Card External
Fault] is detected.
0 : Always Detected
1 : Detected during RUN Only
6 Related Drive Parameters
Default
(Range)
(0 - 3, 7, 8)
(0 - 5)
(1, 3)
(0, 1)
8
1
1
0
35