Termination Resistor Connection - YASKAWA CC-Link SI-C3 Installation Manual

Ac drive option
Hide thumbs Also See for CC-Link SI-C3:
Table of Contents

Advertisement

A - Blade depth of 0.6 mm or less
Figure 5.18 Option Modular Connector CN1 Installation (Ex. GA700)

Termination Resistor Connection

When the CC-Link Option is the last station connected in a CC-Link network, the
termination resistor needs to be installed on that CC-Link Option.
Cut the ring lugs from the termination resistor leads, and then loosen the DA and DB
terminals and insert the termination resistor between terminals DA and DB as shown.
Note:
Use the built-in termination resistor from the master if available, otherwise procure a standard-market resistor
of 110 Ω, ±5% (1/2 W).
A - Jumper
B - Cut here
YASKAWA TOEP C730600 83A CC-Link Installation Manual
B - Blade width of 3.5 mm or less
C - Cut (removes approximately 5.5
Figure 5.19 Termination Resistor
5 Installation Procedure
mm (0.21 in) of the covering at the
tip.)
33