8 CC-Link Data List
Note:
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE
(Frequency Reference 2 flag) too often can shorten the performance life of the drive's internal memory.

D1000 Remote I/O

PLC → D1000
Signal
Name
Run Command/
RY0
Automatic Run
Command
Forced Run
RY1
Command
Terminal S3
RY2
Function
Terminal S4
RY3
Function
Terminal S5
RY4
Function
Terminal S6
RY5
Function
Terminal S7
RY6
Function
Terminal S8
RY7
Function
RY8
Reserved
External Baseblock
RY9
Command
RYA
External Fault [EF0] ON: Option Card External Fault
RYB
Reserved
RYC
Monitor Reference
46
Table 8.3 Remote I/O List (PLC → D1000)
ON: Run Command/Automatic Run Command
OFF: Stop Command
ON: Forced Run Command
OFF: Stop Command
Multi-Function Input: H1-03
Multi-Function Input: H1-04 [Terminal S4 Function
Selection]
Multi-Function Input: H1-05
Multi-Function Input: H1-06
Multi-Function Input: H1-07
Multi-Function Input: H1-08
ON: No converter output
ON: Monitor data specified in the monitor code is set to
remote register RW
R0
Description
-
-
.
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Comments
(Default)
-
-
H1-03 = 24 [External
Fault]
H1-04 = 14 [Fault
Reset]
H1-05= F [Through
Mode]
H1-06= F [Through
Mode]
H1-07= F [Through
Mode]
H1-08 = 8
[Baseblock
command (N.O.)]
-
-
-
-
When switching
between monitors
using RYC (Monitor
Reference), RYC
needs to be turned
OFF and then back
ON again after the
monitor code has
been changed.