9 Troubleshooting
Fault Condition
No Station Name
Bad Station Name
Programmed
Init. Failure
Permanent
Communication Loss
Bad IP
Configuration
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98: Shows the first declared fault since the last power cycle. Only cleared upon
drive power-up.
• U6-99: Shows the present option SI-EP3 status. Cleared upon a network-issued fault
reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the
original fault value and U6-99 stores the new fault status value.

Option Compatibility

You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
• You can only connect one option to the GA500 and HV600 drives. Connect the option to the CN5 connector.
• You can connect two options to an FP605 drive. Connect the communication option to the CN5-A connector.
• Compatible communication options are different for different models. Refer to the drive manuals for more
information.
Option
*1
*1
PG-B3
, PG-X3
*1 *3 *4
PG-RT3
, PG-F3
70
Status
Fault
Value
Declared
(U6-98/
U6-99)
None
1305
None
1306
None
1307
bUS
1308
None
1309
Table 9.2 Option Compatibility
*1 *3 *4
Description
No Station Name has been programmed into the option.
Station Name Programmed is invalid and must be
reprogrammed.
Initialize error on power-up.
Fatal error in MAC/PHY hardware Cycle power.
Invalid IP/subnet/gateway address programmed into F7-01 -
F7-12.
Connector
CN5-B, C
CN5-C
YASKAWA TOEP C730600 89B PROFINET Installation Manual
Number of Options
Possible
*2
2
1