D1000 Remote I/O - YASKAWA SI-C3 Technical Manual

Ac drive option cc-link
Hide thumbs Also See for SI-C3:
Table of Contents

Advertisement

Signal
Name
RXB
Monitoring Motor Revolutions
RXC
Obtain Monitor Data
RXD
Frequency Setting Ready 1
RXE
Frequency Setting Ready 2
Command Code Execute
RXF
Complete
RX10 - 19
Reserved
RX1A
Error
RX1B
Remote Station Ready
RX1C - 1F
Reserved
*1
Terminals are different for different drive models. Refer to
for more information.
Note:
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency Reference 2
flag) too often can shorten the performance life of the drive's internal memory.

D1000 Remote I/O

PLC → D1000
Signal
Name
Run Command/Automatic Run
RY0
Command
RY1
Forced Run Command
RY2
Terminal S3 Function
RY3
Terminal S4 Function
RY4
Terminal S5 Function
RY5
Terminal S6 Function
RY6
Terminal S7 Function
RY7
Terminal S8 Function
RY8
Reserved
RY9
External Baseblock Command
RYA
External Fault [EF0]
RYB
Reserved
RYC
Monitor Reference
RYD, E
Reserved
RYF
Command Code Execute Request Request to execute the command code.
RY10
Terminal M1-M2 Function
RY11
Terminal P1-PC Function
RY12
Terminal P2-PC Function
RY13
Reserved
RY14
Terminal S1 Function
RY15
Terminal S2 Function
RY16
RY17 Enabled/Disabled Selection
YASKAWA SIEP C730600 83E CC-Link Technical Manual
ON: Currently monitoring motor revolutions.
ON: Monitor data has been updated.
ON: Displays the main frequency reference that has been set.
ON: Displays the data set to d1-01 [Frequency Reference 1].
Note:
Also sets the main frequency reference at the same time.
ON: Displayed after the specified command code has been executed.
RXF signal switches OFF when the RYF command is no longer present.
ON: Fault occurred on the drive side.
ON: Drive is ready to operate.
Table 8.3 Remote I/O List (PLC → D1000)
ON: Run Command/Automatic Run Command
OFF: Stop Command
ON: Forced Run Command
OFF: Stop Command
Multi-Function Input: H1-03
Multi-Function Input: H1-04 [Terminal S4 Function Selection]
Multi-Function Input: H1-05
Multi-Function Input: H1-06
Multi-Function Input: H1-07
Multi-Function Input: H1-08
ON: No converter output
ON: Option Card External Fault
ON: Monitor data specified in the monitor code is set to remote register RW
Multi-Function Relay Output 1 (Terminal M1-M2)
*1
Multi-Function Photocoupler Output 1 (Terminal P1-PC)
*1
Multi-Function Photocoupler Output 2 (Terminal P2-PC)
Multi-Function Input: H1-01
Multi-Function Input: H1-02 [Terminal S2 Function Selection]
Description
-
-
Terminals that Change depending on the Model of the Drive on page 35
Description
-
-
-
-
-
8 CC-Link Data List
Comments (Default)
Data is stored in remote register
RW
.
R1
-
-
-
-
-
-
-
-
Comments (Default)
-
-
H1-03 = 24 [External Fault]
H1-04 = 14 [Fault Reset]
H1-05= F [Through Mode]
H1-06= F [Through Mode]
H1-07= F [Through Mode]
H1-08 = 8 [Baseblock command
(N.O.)]
-
-
-
-
When switching between
monitors using RYC (Monitor
Reference), RYC needs to be
.
R0
turned OFF and then back ON
again after the monitor code has
been changed.
-
Triggered by the rising edge of
the signal.
-
-
-
-
H1-01 = 4B [Run Command]
H1-02 = 4C [Stop Command]
-
31