VLT® Midi Drive FC 280
Operating Guide
Downloading the configuration to safety option:
On single-drive systems, via the RS485/USB interface on the drive.
On networked systems, via the RS485 or fieldbus interface on the MCT 10 Safe Plug-in. The control system passes the configura-
tion to the respective safety option.
The feasibility of the configuration is checked when it is downloaded. Further information on configuration and setting parame-
ters for the safety functions is available in the online help for the MCT 10 Safe Plug-in and in the VLT® Motion Control Tool MCT
10 Operating Guide.
The safety option is configured with the commissioning software MCT 10 Set-up Software via a Safe Plug-in. The Safe Plug-in in the
commissioning software is available as default from version 3.18. The commissioning software provides the following menu items
for the safety option:
Safe Input.
Safe Stop 1.
Parameters.
Status.
The menu items are described in detail in the VLT® Motion Control Tool MCT 10 Operating Guide. The menu item Status shows the
following:
Current signal states of inputs and output.
Option operating mode.
Active safety function.
The states of the inputs and output cannot be changed via the commissioning software.
6.7.1.2 Commissioning the Safety Option
This procedure describes the example of the safety option commissioning procedure with VLT® Motion Control Tool MCT 10. In this
example:
A VLT® PROFINET MCA 120 option is installed in the drive and PROFIsafe communication is required for the application.
If any errors occur while changing the password or after the approval step, the Safety plug-in shows a notification with the error
description.
If STO is inactive (the drive is operational) when starting the customization process, the Safety plug-in shows the Confirmation
Required dialog box. This dialog box prompts the user to confirm that STO is activated during the commissioning:
74 | Danfoss A/S © 2022.02