Installation Check List - Danfoss VLT FC 280 Operating Manual

Midi drive with functional safety over fieldbus
Hide thumbs Also See for VLT FC 280:
Table of Contents

Advertisement

VLT® Midi Drive FC 280
Operating Guide
61
68
69
Illustration 21: Serial Communication Wiring Diagram
For basic serial communication set-up, select the following:
Protocol type in parameter 8-30 Protocol.
Drive address in parameter 8-31 Address.
Baud rate in parameter 8-32 Baud Rate.
Two communication protocols are internal to the drive.
Danfoss FC
Modbus RTU
Follow motor manufacturer wiring requirements.
Functions can be programmed remotely using the protocol software and RS485 connection, or in parameter group 8-** Communica-
tions and Options.
Selecting a specific communication protocol changes various default parameter settings to match the specifications of the protocol
and makes extra protocol-specific parameters available.

4.10 Installation Check List

Before completing installation of the unit, inspect the entire installation as detailed in
completed.
Table 5: Installation Check List
Inspect for
Description
Auxiliary equip-
Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers, residing on the
ment
input power side of the drive, or output side to the motor. Ensure that they are ready for full-speed
operation.
Check the function and installation of any sensors used for feedback to the drive.
Remove any power factor correction capacitors on the motor.
Adjust any power factor correction capacitors on the mains side and ensure that they are dampened.
Cable routing
Ensure that the motor wiring and control wiring are separated, shielded, or in 3 separate metallic con-
duits for high frequency interference isolation.
Control wiring
Check for broken or damaged wires and loose connections.
Check that the control wiring is isolated from power and motor wiring for noise immunity.
Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly.
Cooling clear-
Ensure that the top and bottom clearance is adequate to ensure proper airflow for cooling, see chap-
ance
ter Mounting.
Danfoss A/S © 2022.02
+
RS485
Electrical Installation
Table
5. Check and mark the items when
AQ381425076031en-000101 / 130R1223 | 33