VLT® Midi Drive FC 280
Operating Guide
Bit
Description
2–3
Reserved
4
Blank initial state
5
Safe fieldbus support
6
7
8
Safe function status on safe fieldbus
9
Safe fieldbus communication established
10–31
Reserved
6.7.1.5 Copying Safe Parameter Set-up
To copy the safe parameter set-up to another drive, see the following steps:
Procedure
1.
Prepare a commissioning report.
2.
Select [1] All to LCP in parameter 0-50 LCP Copy. Monitor the upload on the progress bar.
3.
Install the LCP with all the copied parameters on the drive that needs to be updated.
4.
Select [2] All from LCP in parameter 0-50 LCP Copy. The normal password protection can be applied in parameter 0-60 Main
Menu Password.
5.
Enter the password for copied SO configuration (= safe parameters) from LCP.
6.
Accept the download of the safe parameters to the drive, which now has a new configuration assigned to it.
7.
Reset the drive to activate the new configuration.
6.7.1.6 Password Protection LCP Copy and Safe Parameter Mismatch
Optionally, a password protection can be used for the function LCP copy (see
Table
41). Password protection can be enabled/disabled in parameter 0-69 Password Protection of Safety Parameters. The password is
set in parameter 0-68 Safety Parameters Password. Default password is 300.
84 | Danfoss A/S © 2022.02
State
0: inactive
1: active
0: no safe fieldbus supported
1: PROFIsafe supported
2: FSoE supported
3: CIP Safey supported
4: openSAFETY supported
0: deactivated
1: activated, safe fieldbus communication is established.
0: not established
1: established
Table
40) and if there is a parameter mismatch (see
Safety Functions
AQ381425076031en-000101 / 130R1223