VLT® Midi Drive FC 280
Operating Guide
6.3.2.1 SS1-t Triggered by DI
To enable safe DI as SS1-t input, set parameter 42-20 Safe Function as [9] SS1-t. The following table shows SS1-t statuses based on
whether terminals 37 and 38 are energized.
Table 27: SS1-t via DI
Previous status
Inactive
Timing
Timing
Timer expired
Voltage range is 24 V±15%, with terminal 39 as reference.
1
Open circuit or the voltage within the range of 0 V±1.5 V, with terminal 39 as reference.
2
When setting parameter 0-2* LCP Display=[4285].
3
Parameter 42-24 Restart Behavior=[0] Manual.
4
Parameter 42-24 Restart Behavior=[1] Automatic, and no SS1-t request on fieldbus (inactive command or disabled).
5
6.3.2.2 SS1-t Triggered by Fieldbus
To enable safety fieldbus protocol, set parameter 42-60 Telegram Selection to [1] PROFIsafe Std. Tel. 30. SS1-t control command is sent
from the upper device continuously and periodically. The command includes:
SS1-t inactive
SS1-t active
Table 28: SS1-t via Fieldbus
Previous status
Inactive
Timing
Timer expired
See the table in
6.5.2.5.1 PROFIsafe Control
1
When setting parameter 0-2* LCP Display=[4285].
2
Danfoss A/S © 2022.02
Terminal 37
Terminal 38
High
High
(1)
High→Low
High→Low
(2)
High→Low
High
High
High→Low
High
High
Low
X
X
Low
X
X
SS1-t command
(1)
Inactive
Inactive→active
Active
Inactive
Active
Inactive
Word.
Status
Inactive
Timer start
Timer start
Timer start
Timing
(4)
Timer stop & reset
(5)
Timing
STO
Status
Inactive
Timer start
Timing
Timer stop & reset
STO
Inactive
AQ381425076031en-000101 / 130R1223 | 61
Safety Functions
LCP display
None
SS1-t
(3)
W252
W252
SS1-t
None
SS1-t
W68
LCP display
None
SS1-t
(2)
None
W68
None