Synchronizing Drive Data To A New Memory Module (Create Drive Backup); Copying Data To Another Drive; Copying Data To Multiple Drives - Danfoss VLT FC 280 Operating Manual

Midi drive with functional safety over fieldbus
Hide thumbs Also See for VLT FC 280:
Table of Contents

Advertisement

VLT® Midi Drive FC 280
Operating Guide
AVOID UNINTENTIONAL OVERWRITING
The default setting of parameter 31-40 Memory Module Function is [1] Only Allow Download. If there is any update, such as firm-
ware updated by MCT 10 using OSS file, parameter updated by LCP or bus, parameters reset via parameter 14-22 Operation Mode,
or 3-finger-reset of the drive, the updated data will be lost after a new power cycle, because the drive downloads data from the
memory module again.
-
After the data has been downloaded from the memory module to the drive, select [0] Disabled or [2] Only Allow Upload in
parameter 31-40 Memory Module Function before the new power cycle.

5.9.2 Synchronizing Drive Data to a New Memory Module (Create Drive Backup)

To avoid unintentional overwriting of the data in the memory module, consider to adjust the settings for parameter 31-40 Memo-
ry Module Function before next power cycle according to different operating purpose.
Procedure
1.
Plug a new empty memory module in the drive.
2.
Select [2] Only Allow Upload or [3] Allow Both Download and Upload in parameter 31-40 Memory Module Function.
3.
Power up the drive.
4.
Wait until the synchronization is complete, refer to
tions on the drive.

5.9.3 Copying Data to Another Drive

To avoid unintentional overwriting of the data in the memory module, consider to adjust the settings for parameter 31-40 Memo-
ry Module Function before next power cycle according to different operating purpose.
Procedure
1.
Make sure that the required data is uploaded to the memory module, refer to
Memory Module (Create Drive
2.
Unplug the memory module and plug into a new drive.
3.
Make sure that [1] Only Allow Download or [3] Allow Both Download and Upload is selected in parameter 31-40 Memory Mod-
ule Function on the new drive.
4.
Power up the new drive.
5.
Wait until the download is complete and the data is transferred, refer to
check the transfer indications on the drive.

5.9.4 Copying Data to Multiple Drives

If multiple drives are of same voltage/power, the information of 1 drive can be transferred to the others via 1 memory module.
The data can also be downloaded to the memory module from a PC via the VLT® Memory Module Programmer.
In any of the drives, if an empty memory module is plugged in for backing up data, adjust the settings for parameter 31-40 Memo-
ry Module Function to [2] Only Allow Upload or [3] Allow Both Download and Upload before next power cycle.
Procedure
Danfoss A/S © 2022.02
N O T I C E
N O T I C E
5.9.8 Transfer Performance and Indications
N O T I C E
Backup).
N O T I C E
N O T I C E
to check the transfer indica-
5.9.2 Synchronizing Drive Data to a New
5.9.8 Transfer Performance and Indications
AQ381425076031en-000101 / 130R1223 | 51
Commissioning
to

Advertisement

Table of Contents
loading