Danfoss VLT FC 280 Operating Manual page 124

Midi drive with functional safety over fieldbus
Hide thumbs Also See for VLT FC 280:
Table of Contents

Advertisement

VLT® Midi Drive FC 280
Operating Guide
9.6.7 Control Card, +10 V DC Output
Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
9.6.8 Control Card, RS485 Serial Communication
Terminal number
Terminal number 61
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV). It is used in production, and not rec-
ommended for fieldbus application.
9.6.9 Control Card, USB Serial Communication
USB standard
USB plug
Connection to the PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protective earth. Use only an isolated laptop as PC connection to the
USB connector on the drive.
9.6.10 Relay Outputs
Programmable relay outputs
Relay 01
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
@ cosφ 0.4)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
@ cosφ 0.4)
Maximum terminal load (DC-1)
Minimum terminal load on 01–03 (NC), 01–02 (NO)
IEC 60947 parts 4 and 5.
1
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation.
9.6.11 Control Card Performance
Scan interval
9.6.12 Control Characteristics
Resolution of output frequency at 0–500 Hz
System response time (terminals 18, 19, 27, 29, 32, and 33)
Speed control range (open loop)
Speed accuracy (open loop)
Speed accuracy (closed loop)
All control characteristics are based on a 4-pole asynchronous motor.
124 | Danfoss A/S © 2022.02
on 01–02 (NO) (resistive load)
(1)
on 01–02 (NO) (inductive load
(1)
on 01–02 (NO) (resistive load)
(1)
on 01–02 (NO) (inductive load)
(1)
on 01–03 (NC) (resistive load)
(1)
on 01–03 (NC) (inductive load
(1)
on 01–03 (NC) (resistive load)
(1)
Specifications
10.5 V ±0.5 V
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
1.1 (full speed)
USB type B plug
01–03 (NC), 01–02 (NO)
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC 10 mA, 24 V AC 20 mA
±0.003 Hz
1:100 of synchronous speed
±0.5% of nominal speed
±0.1% of nominal speed
AQ381425076031en-000101 / 130R1223
50
15 mA
1
1 ms
≤2 ms

Advertisement