VLT® Midi Drive FC 280
Operating Guide
Bit
Name
9
SFBC initialized
10
Safe fieldbus acknowl-
edge request
11
Internal failure
12
Reset Required
13
Pending fail safe state
14
External failure
15
Safe function pending
16
General reset
17
Customization confirmed
18
Customization aborted
19
Customization requested
20
Reserved
21
PUST warning
22–23
Reserved
24–31
Error code
Table 49: Status Word 2
Bit
Name
0–1
DI safety status
2–3
Reserved
100 | Danfoss A/S © 2022.02
Description
0: Not in SFBC initialized state.
1: In SFBC initialized state.
Indicating if the PROFIsafe PLC is requesting operator acknowledge or not.
0: No operator acknowledgment requested.
1: Operator acknowledgment requested from safe PLC.
0: No internal failure is active.
1: An internal failure is active.
0: No SFBC reset is required.
1: A SFBC reset is required.
0: No pending fail safe state.
1: In pending fail safe state.
0: No external failure is active.
1: An external failure is active.
0: No safe function is pending.
1: A safe function is pending.
0: No change in state.
1: A General Reset is done.
0: No change in state.
1: Customization confirmed.
0: No change in state.
1: Customization aborted.
0: No change in state.
1: Customization is requested.
0: No change in state.
1: A power-up selftest warning is issued.
This is the internal or external error codes. 8 bits can indicate 256 different errors. Refer to
6.10.3 Troubleshooting
for the definition of the error codes.
Description
00: Inactive
01: Active
10: Pending
11: Error
Safety Functions
AQ381425076031en-000101 / 130R1223