VLT® Midi Drive FC 280
Operating Guide
Inspect for
Description
Ambient condi-
Check that requirements for ambient conditions are met.
tions
Fusing and cir-
Check for proper fusing or circuit breakers.
cuit breakers
Check that all fuses are inserted firmly and are in operational condition, and that all circuit breakers
are in the open position.
Grounding
Check for sufficient ground connections and ensure that those connections are tight and free of oxi-
dation.
Grounding to conduit, or mounting the back panel to a metal surface, is not a suitable grounding.
Input and out-
Check for loose connections.
put power wir-
Check that the motor and mains cables are in separate conduit or separated shielded cables.
ing
Panel interior
Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
Check that the unit is mounted on an unpainted metal surface.
Switches
Ensure that all switch and disconnect settings are in the proper positions.
Vibration
Check that the unit is mounted solidly, or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
-
Ensure that all safety covers are in place and securely fastened before applying power.
34 | Danfoss A/S © 2022.02
C A U T I O N
Electrical Installation
AQ381425076031en-000101 / 130R1223