Part Replacement Service Window; Iom Replacement - Western Digital Ultrastar Data60 User Manual

Hide thumbs Also See for Ultrastar Data60:
Table of Contents

Advertisement

User Guide
4.1   Part Replacement Service Window
The following table contains a time required and a replacement window related to each hot swappable
replacement part within the enclosure. The time required for replacement is the expected amount of time it
requires to replace the part. The replacement window is the amount of time that the enclosure can be open
for servicing. If the enclosure cover is open for a period lasting longer than the replacement window, the
enclosure may reduce access to drives and other components to reduce the occurrence of thermal issues.
Table 36: Replacement Service Window
Attention: In the case of multiple part failures, a failed fan should always be replaced before
any other part is replaced. Once the enclosure cover is open, the failed fan must be removed
within a minute. The remainder of the replacement of a failed fan should be completed within
the 5 minute replacement window.
4.2   IOM Replacement
Table 37: Replacement Procedure Info
Required Tools
None
Step 1 : Grasp both handles at the front of the enclosure and pull with even pressure to extend the
chassis out of the rack until it is stopped by the safety latches. The safety latches will prevent the
enclosure from coming out of the rack completely and the cover will remain in the rack attached
to the rear alignment brackets.
Part
IOM
PSU
Rear Fan
IOM Fan
Drive Assembly
# of People Required
1

4.1 Part Replacement Service Window

Time Required
60s
60s
60s
60s
60s
Time Required
60s
4. Part Replacement
Replacement Window
5 Minutes
5 Minutes
5 Minutes
5 Minutes
5 Minutes
Replacement Window
5 Minutes