Western Digital Overview This section provides an overview of rack requirements and recommendations. In This Chapter: - Ultrastar Data102 Rack Requirements..2 - Rack Safety............. 3 - CMA Standard Recommended Racks...4 - CMA Lite Recommended Racks....5 - Vertical Rack Rail Settings......6 - Recommended PDUs and Available Installation Space..........7...
1.1 Ultrastar Data102 Rack Requirements The Ultrastar Data102 is designed to be installed into a rack that meets the EIA-310 standard at a minimum 1181-1197 mm (46.5in. - 47.13in.) of usable rack space, frame to frame. The vertical rack rails must be set between 812.8mm - 914.4mm / 32 in.
1.2 Rack Safety When extended out of the rack on the rail system, the Ultrastar Data102 will be ~950 mm / 37.4in. extended outward. This may be a potential tipping hazard depending on the configuration of the rack. Ensure that leveling feet, anti-tilt, and any other safety features recommended by the specific rack manufacturers have been deployed before servicing.
1.3 CMA Standard Recommended Racks Figure 2: Shipping Bracket Screw Locations 1.3 CMA Standard Recommended Racks The following is a list of racks that are recommended for the Ultrastar Data102 using CMA Standard. Table 2: Recommended Racks Rack Vendor...
H: in. x W: in. x D: in. w/ Rack Extender 1.4 CMA Lite Recommended Racks The following is a list of racks that are recommended for the Ultrastar Data102 using CMA Lite. Table 3: Recommended Racks Rack Vendor...
Page 11
1. Overview Recommended Rack Configurations 1.4 CMA Lite Recommended Racks Rack Vendor Part Number Dimensions Notes Units with the front door stiffeners or the door latch in the CMA Lite configuration. WEDIT604 H: 2178.1mm x W: 609.6mm x D: The enclosure 1317.6mm/ cannot be H: 85.75in.
1. Overview Recommended Rack Configurations 1.5 Vertical Rack Rail Settings 1.5 Vertical Rack Rail Settings The vertical rack rails should be adjusted to the specified measurements in all of the recommended rack configurations to ensure the enclosure and cable management fit properly. After the front and rear vertical rack rails have been adjusted the enclosure rails can be extended or retracted to best fit these adjustments.
Recommended Rack 1. Overview Configurations 1.6 Recommended PDUs and Available Installation Space 1.6 Recommended PDUs and Available Installation Space The following is a list of available PDU space that is recommended for use in each rack. Table 4: Available PDU Space Rack Model PDU Orientation...
Page 14
Recommended Rack 1. Overview Configurations 1.6 Recommended PDUs and Available Installation Space Figure 5: PDU in the Zero Space...
Western Digital CMA Standard Rack Specifications This section provides information related to the recommended rack models, compatible PDUs, and required accessories and hardware using CMA Standard. Each rack recommendation comes with information specific to what PDUs are approved and what hardware is required to mount them.
2. CMA Standard Rack Specifications Recommended Rack Configurations 2.3 TRIPP LITE Model Number Rack Units Dimensions H: 96.25in. x W: 24in. x D: 51.8in. Table 9: Compatible PDUs Model Number Width Depth Orientation Server Technology STV-4501 55.5mm / 2.18in. 86.15mm / 3.39in. Rear STV-4502 55.5mm / 2.18in.
Western Digital CMA Lite Rack Specifications This section provides information related to the recommended rack models, compatible PDUs, and required accessories and hardware using CMA Lite. Each rack recommendation comes with information specific to what PDUs are approved and what hardware is required to mount them.
3. CMA Lite Rack Specifications Recommended Rack Configurations 3.3 TRIPP LITE Model Number Rack Units Dimensions H: 96.25in. x W: 24in. x D: 51.8in. Table 22: Compatible PDUs Model Number Width Depth Orientation Server Technology STV-4501 55.5mm / 2.18in. 86.15mm / 3.39in. Rear STV-4502 55.5mm / 2.18in.
Western Digital Installation In This Chapter: - PDU Mounting Bracket Installation (KIT- MBVPT-1B)............19 - PDU Mounting Bracket Installation (KIT- MB-40).............25...
Recommended Rack 4. Installation Configurations 4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B) 4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B) The installation of PDU mounting bracket kit (KIT-MBVPT-1B) for the AFCO, TRIPPLITE, and CRENLO racks extends the PDUs farther back in the rack to allow for more room for the CMA and enclosure. Note: For recommended vertical rack rail settings, see: Vertical Rack Rail Settings (page Table 31: Procedure Info...
Page 25
Recommended Rack 4. Installation Configurations 4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B) Figure 7: Flat Bracket Installation (bottom) d. Align the right-angle bracket behind the flat bracket over the holes on the left-hand side of the flat bracket. e. Slide the washers onto the mounting bolts and secure the right-angle bracket to the backer plate through the flat bracket.
Page 26
Recommended Rack 4. Installation Configurations 4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B) Figure 9: Right-Angle Bracket Installed (bottom) Figure 10: Flush Right-Angle Bracket (bottom) Step 2 : Install the top side bracket using the provided hardware. a. Locate the two screw holes at the top of the back side of the PDU. b.
Page 27
Recommended Rack 4. Installation Configurations 4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B) Figure 11: Flat Bracket (top) c. Secure the flat bracket to the PDU by using the screws provided in the PDU mounting kit as shown in the image below. Figure 12: Flat Bracket Installation (top) d.
Page 29
Recommended Rack 4. Installation Configurations 4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B) Figure 15: Flush Right-Angle Bracket (top) Step 3 : Install the PDU into the rear of the rack. a. Locate the top row of holes on the top vertical rail. b.
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Figure 17: PDU Installation (bottom) Figure 18: PDU Distance from Rack Rear Rail 4.2 PDU Mounting Bracket Installation (KIT-MB-40) The installation of PDU mounting bracket kit (KIT-MB-40) for the AFCO, TRIPPLITE, and CRENLO racks extends the PDUs farther back in the rack to allow for more room for the CMA and enclosure.
Page 31
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Note: For recommended vertical rack rail settings, see: Vertical Rack Rail Settings (page Table 32: Procedure Info # of People Required Tools Required Parts Required • # 2 Philips Screwdriver •...
Page 32
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Figure 19: Locate PDU Mounting Buttons b. Remove the screws that secure the PDU mounting buttons using the # 2 Philips Screwdriver. Step 2 : Mount the PDU mounting buttons onto the angle-bracket. a.
Page 33
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Figure 20: Install the PDU Mounting Button onto the Angle Bracket b. Repeat the previous step to install the PDU mounting button on the remaining angle-bracket. Step 3 : Install the angle-bracket to the bottom of the PDU using the provided hardware. a.
Page 34
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Figure 21: Install the Angle Bracket on the PDU (Bottom) Step 4 : Install the angle-bracket to the top of the PDU using the provided hardware. a. Locate the two screw holes at the top of the back side of the PDU. b.
Page 35
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Figure 22: Install the Angle Bracket on the PDU (Top) Step 5 : Install the PDU into the rear of the rack. a. Locate the middle set of keyholes on the rear vertical rack rails. b.
Page 37
Recommended Rack 4. Installation Configurations 4.2 PDU Mounting Bracket Installation (KIT-MB-40) Figure 24: PDU Installed into Keyholes c. Verify that the PDU is secure by pressing on the front of the PDU. If the PDU does not shift, it is properly mounted. If the PDU does shift, remove the PDU and repeat the PDU installation step to ensure it is secure.
Need help?
Do you have a question about the Ultrastar Data102 and is the answer not in the manual?
Questions and answers