When removing a fan module, do not rock it back and forth. Rocking fans can
Caution -
damage the fan module connectors.
When changing fan modules, note that only the fan modules can be removed or
Caution -
replaced. Do not service any other components in the fan compartment unless the server is shut
down and the power cords are removed.
6.
Install a new fan module.
See
"Install a Fan Module" on page
Related Information
"Determine Which Fan Module Is Faulty" on page 71
"Extend the Server to the Service Position" on page 49
"Install a Fan Module" on page 73

Install a Fan Module

To ensure proper cooling, ensure that you install the replacement fan module in the
Caution -
same slot from which the faulty fan was removed.
1.
Unpack the replacement fan module and place it on an antistatic mat.
2.
Open the fan door.
73.
Install a Fan Module
Servicing Fan Modules
73