Installation; Installing The Units - Siemens Simovert Masterdrives Compact Plus Series Operating Instructions Manual

Motion control frequency inverter (dc-ac)
Table of Contents

Advertisement

Available languages

Available languages

06.2006
5

Installation

5.1

Installing the units

WARNING
NOTE
Clearances
Siemens AG
6SE7087-6KP50
SIMOVERT MASTERDRIVES
Safe converter operation requires that the equipment is mounted and
commissioned by qualified personnel taking into account the warning
information provided in these Operating Instructions.
The general and domestic installation and safety regulations for work
on electrical power equipment (e.g. VDE, UL) must be observed as well
as the professional handling of tools and the use of personal protective
equipment.
Death, severe bodily injury or significant material damage could result if
these instructions are not followed.
MASTERDRIVES components are designed in accordance with degree
of protection IP20 or IBXXB in accordance with EN 60529 and as open-
type devices to UL 50, thus providing protection against electrical
shocks. In order to also ensure protection against mechanical and
climatic stresses the components have to be operated in
housings/cabinets/rooms that are designed according to the
requirements of' EN 60529 and classified as enclosure type to UL 50.
When you install the equipment, make sure that the DC link connection
is at the top and the motor connection is at the bottom.
The devices must be mounted side by side in close physical contact.
In order to ensure an adequate supply of cooling air, a clearance of
100 mm must be left at the top of the unit and at the bottom of the unit
respectively to components which may considerably affect the flow of
cooling air.
When mounting in cabinets, the cabinet cooling must be designed
according to the power loss. Please refer to the Technical Data in this
regard.
Operating Instructions
Installation
5-1