The Converter As Ethernet Node - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

6.6.5

The converter as Ethernet node

Integrating a converter into an Ethernet network (assigning an IP address)
Procedure
1. Set p8924 (PN DHCP mode) = 2 or 3
– p8924 = 2: The DHCP server assigns the IP address based on the MAC address of the
– p8924 = 3: The DHCP server assigns the IP address based on the device name of the
2. Save the settings with p8925 = 2. The next time that the converter switches on, it retrieves
the IP address, and you can address the converter as Ethernet node.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the Ethernet/IP command "Set Attribute Single" (class F5 hex, attribute 3).
The following options are available:
• via an Ethernet/IP controller
• via an Ethernet/IP commissioning tool
You have now integrated the converter into Ethernet.
Displays
r8930: Device name of the converter
r8934: Operating mode, PN or DHCP
r8935: MAC address
Additional information
You can find information about parameters and messages (A08565) in the List Manual.
You can also integrate the converter into an Ethernet network by using Proneta or STEP 7.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
converter.