Wiring
4.12 Connecting the digital inputs and outputs
Glanded variant
Digital inputs (X07, X08) and bidirectional digital inputs/outputs (X05)
Cable gland size: M16 * 1.5
Note
Malfunction caused by incorrect switching states as the result of diagnostic flows in off
state (logical state "0")
In contrast to mechanical switching contacts, e.g. emergency stop switches, diagnostic flows
can also flow with semiconductor switches in the off state. If interconnection with digital
inputs is faulty, the diagnostic flows can lead to incorrect switching states and thus to a
malfunction of the drive.
• Observe the conditions for digital inputs and digital outputs specified in the relevant
manufacturers documentation.
• Check the conditions of the digital inputs and digital outputs in regard to the flows in off
state. If applicable, connect the digital inputs with suitably dimensioned, external resistors
to protect against the reference potential of the digital inputs.
Further information
72
Cables and connectors (Page 57)
X07
Signal
Description
1L+
Unswitched 24 V
DI0
Digital input 0
DI1
Digital input 1
1M
Unswitched 0 V
FE
Functional earth
X08
Signal
Description
1L+
Unswitched 24 V
DI2
Digital input 2
DI3
Digital input 3
1M
Unswitched 0 V
FE
Functional earth
X05
Signal
Description
2L+
Switched 24 V
DIO24
Bidirectional digital output/input
24
DIO25
Bidirectional digital output/input
25
2M
Switched 0 V
FE
Functional earth
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive