Electromechanical Potentiometer - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Parameter
r1077
r2050[0...11] CO: PROFIdrive PZD receive word
Further information
For further information refer to the function diagrams 2468, 9360 and 3030 of the List
Manual.
6.14.3

Electromechanical potentiometer

The converter has two electromechanical potentiometers.
The potentiometers are hardwired with the internal analog inputs 0 and 1.
Setting the potentiometer as setpoint source
Parameter
p1070[0] = 755[0]
p1070[1] = 755[1]
p1075[0] = 755[0]
p1075[1] = 755[1]
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Description
CO: Supplementary setpoint effec-
tive
Description
Main setpoint
Interconnect the main setpoint with the internal analog inputs 0 and 1.
Additional setpoint
Interconnect the additional setpoint with the internal analog inputs 0 and 1.
Advanced commissioning
Setting
Displays the effective supplementary setpoint.
Connector output to interconnect the PZD re-
ceived from the fieldbus controller in the word
format.
[1] Most standard telegrams receive the speed
setpoint as receive word PZD02.
6.14 Setpoints
203