Standard asynchronous motors up to a rated power of approximately 3 kW are normally
connected in a star/delta connection (Y/Δ) at 400 V/230 V. For a 400 V line supply, you can
connect the motor to the converter either in a star or in a delta connection.
Function description
Operating the motor in a star connection
66
Cables and connectors (Page 57)
Signal
Description
U
Phase U
V
Phase V
W
Phase W
EM+
EM brake positive (180 V DC)
EM-
EM brake negative (180 V DC)
T+
Motor temperature sensor positive
T-
Motor temperature sensor negative
Protective earth
Screw tightening torque:
U/V/W: 1.0 Nm/8.9 lbf.in;
: 2.2 Nm/19.5 lbf.in
Cable gland size: M25 * 1.5
In a star connection, the motor can provide its
rated torque M
in the range 0 ... rated fre-
N
quency f
.
N
Rated voltage U
= 400 V is available at a rated
N
frequency f
= 50 Hz.
N
The motor goes into field weakening above
the rated frequency. In field weakening, the
available motor torque decreases linearly with
1/f. In field weakening, the available power
remains constant.